North American split-phase inverter (battery voltage48V)

| Technical specification | R5KH1NA | R6KH1NA | R8KH1NA | R10KH1NA |
| Input (PV) | ||||
| Max.power(kW) | 7.5 | 9 | 12 | 13 |
| Max. DC voltage(V) | 500 | |||
| MPPT voltage range(V) | 125-500 | |||
| Max.input current of single MPPT(A) | 12 | |||
| MPPT tracker/strings | 4/1 | |||
| AC output | ||||
| Rated output power(kVA) | 5 | 6 | 8 | 10 |
| Max. output current(A) | 24 | 28.8 | 38.3 | 47.8 |
| Ac output voltage(V) | 120/240(split phase), 208(2/3 phase),230 (single phase) | |||
| Frequency (Hz) | 50/60 | |||
| PF | 0.8lagging-0.8leading | |||
| THDi | < 3% | |||
| AC output topology | Split phase, 2/3 phase, single phase | |||
| Battery | ||||
| Battery voltage range(V) | 40~58 | |||
| Max. charging voltage(V) | 58 | |||
| Max.charge/discharge current(A) | 120/120 | 135/135 | 190/190 | 210/210 |
| Battery type | lithium /Lead-acid | |||
| Communication interface | CAN/RS485 | |||
| EPS output | ||||
| Rated power (kVA) | 5 | 6 | 8 | 10 |
| Rated output voltage(V) | 120/240 (split phase), 208 (2/3 phase),230 (single phase) | |||
| Rated output current(A) | 24 | 28.8 | 38.3 | 47.8 |
| Rated frequency (Hz) | 50/60 | |||
| Automatic switch over time (ms) | < 20 | |||
| THDu | < 2% | |||
| Overload capacity | 125%,60S/150%,1S | |||
| General data | ||||
| Max. efficiency | ≥98.2% | |||
| CEC efficiency | ≥97.2% | |||
| Protection class | IP65/NEMA 3R | |||
| Noise emission (dB) | < 25 | < 29 | < 29 | < 29 |
| Operation temperature | - 25℃~ 60℃ | |||
| Cooling | Natural | |||
| Relative humidity | 0 ~95%(non-condensing) | |||
| Altitude | 2,000m | |||
| Dimensions W*D*H (mm) | 430*220*710 | |||
| Self-consumption(W) | < 3 | |||
| Weight (kg) | 41 | |||
| Display and communication | ||||
| Display | LCD, touch screen | |||
| Interface:RS485/Wifi/4G/CAN/DRM | Yes | |||
| Standby power consumption at night(W) | < 2.5 (With the battery < 5 ) | |||
| Isolation transformer | No | |||
| safety standard | UL1741SA all options, UL1699B, CSA 22.2 | |||
| EMC | FCC Part 15, Class B | |||
| On-grid | IEEE 1547, IEEE 2030.5, Hawaii Rule 14H, Rule 21 Phase I,II,III,NRS | |||